Bewacard 610 Technical Manual 9
Installation continued
The numbers below refer to the numbers on the wiring diagram.
1
Electric locking device. Dashed line shows connection to locks with
fail unlocked operation.
2
Power in, terminal block nos. 1 and 2.
3
Exit Request button. To operate short terminal nos. 6 and 9.
Optionally, a time-clock can be connected to control a door that should
be permanently open.
4
Input for reader inhibit. To operate short terminal nos. 7 and 9. The
red LED on the fascia will be lit.
5
Duress output. Used for activating an external alarm. Use an E7 relay.
Connect between terminal nos. 8 and + (1).
6
Remove the jumper if back lighting is not required.
7
Control input for Common code. Terminal nos. 10 and 13 open:
Common code enabled. Terminal nos. 10 and 13 linked: Common code
disabled.
8
Control input of Card and Card + PIN security levels. Terminal nos.
11 and 13 open: Card. Terminal nos. 11 and 13 linked: Card + PIN.
9
Control input for Toggle function. Link terminal nos. 12 and 13 to
activate the toggle function.
10
The SW1 push button. Used to erase the memory and to set a new
password.
11
Tamper switch. Normally closed when the housing is closed.